105 changes: 9 additions & 96 deletions lib/openstudio-standards/standards/Standards.AirLoopHVAC.rb
Original file line number Diff line number Diff line change
Expand Up @@ -270,103 +270,16 @@ def air_loop_hvac_optimum_start_required?(air_loop_hvac)
# @param air_loop_hvac [OpenStudio::Model::AirLoopHVAC] air loop
# @return [Boolean] returns true if successful, false if not
def air_loop_hvac_enable_optimum_start(air_loop_hvac)
# Get the heating and cooling setpoint schedules
# for all zones on this airloop.
htg_clg_schs = []
air_loop_hvac.thermalZones.each do |zone|
# Skip zones with no thermostat
next if zone.thermostatSetpointDualSetpoint.empty?

# Get the heating and cooling setpoint schedules
tstat = zone.thermostatSetpointDualSetpoint.get
htg_sch = nil
if tstat.heatingSetpointTemperatureSchedule.is_initialized
htg_sch = tstat.heatingSetpointTemperatureSchedule.get
else
OpenStudio.logFree(OpenStudio::Warn, 'openstudio.standards.AirLoopHVAC', "For #{zone.name}: Cannot find a heating setpoint schedule for this zone, cannot apply optimum start control.")
next
end
clg_sch = nil
if tstat.coolingSetpointTemperatureSchedule.is_initialized
clg_sch = tstat.coolingSetpointTemperatureSchedule.get
else
OpenStudio.logFree(OpenStudio::Warn, 'openstudio.standards.AirLoopHVAC', "For #{zone.name}: Cannot find a cooling setpoint schedule for this zone, cannot apply optimum start control.")
next
end
htg_clg_schs << [htg_sch, clg_sch]
end

# Clean name of airloop
loop_name_clean = air_loop_hvac.name.get.to_s.gsub(/\W/, '').delete('_')
# If the name starts with a number, prepend with a letter
if loop_name_clean[0] =~ /[0-9]/
loop_name_clean = "SYS#{loop_name_clean}"
end

# Sensors
oat_db_c_sen = OpenStudio::Model::EnergyManagementSystemSensor.new(air_loop_hvac.model, 'Site Outdoor Air Drybulb Temperature')
oat_db_c_sen.setName('OAT')
oat_db_c_sen.setKeyName('Environment')

# Make a program for each unique set of schedules.
# For most air loops, all zones will have the same
# pair of schedules.
htg_clg_schs.uniq.each_with_index do |htg_clg_sch, i|
htg_sch = htg_clg_sch[0]
clg_sch = htg_clg_sch[1]

if htg_sch.to_ScheduleConstant.is_initialized
htg_sch_type = 'Schedule:Constant'
elsif htg_sch.to_ScheduleCompact.is_initialized
htg_sch_type = 'Schedule:Compact'
else
htg_sch_type = 'Schedule:Year'
end

if clg_sch.to_ScheduleCompact.is_initialized
clg_sch_type = 'Schedule:Constant'
elsif clg_sch.to_ScheduleCompact.is_initialized
clg_sch_type = 'Schedule:Compact'
else
clg_sch_type = 'Schedule:Year'
end

# Actuators
htg_sch_act = OpenStudio::Model::EnergyManagementSystemActuator.new(htg_sch, htg_sch_type, 'Schedule Value')
htg_sch_act.setName("#{loop_name_clean}HtgSch#{i}")

clg_sch_act = OpenStudio::Model::EnergyManagementSystemActuator.new(clg_sch, clg_sch_type, 'Schedule Value')
clg_sch_act.setName("#{loop_name_clean}ClgSch#{i}")

# Programs
optstart_prg = OpenStudio::Model::EnergyManagementSystemProgram.new(air_loop_hvac.model)
optstart_prg.setName("#{loop_name_clean}OptimumStartProg#{i}")
optstart_prg_body = <<-EMS
IF DaylightSavings==0 && DayOfWeek>1 && Hour==5 && #{oat_db_c_sen.handle}<23.9 && #{oat_db_c_sen.handle}>1.7
SET #{clg_sch_act.handle} = 29.4
SET #{htg_sch_act.handle} = 15.6
ELSEIF DaylightSavings==0 && DayOfWeek==1 && Hour==7 && #{oat_db_c_sen.handle}<23.9 && #{oat_db_c_sen.handle}>1.7
SET #{clg_sch_act.handle} = 29.4
SET #{htg_sch_act.handle} = 15.6
ELSEIF DaylightSavings==1 && DayOfWeek>1 && Hour==4 && #{oat_db_c_sen.handle}<23.9 && #{oat_db_c_sen.handle}>1.7
SET #{clg_sch_act.handle} = 29.4
SET #{htg_sch_act.handle} = 15.6
ELSEIF DaylightSavings==1 && DayOfWeek==1 && Hour==6 && #{oat_db_c_sen.handle}<23.9 && #{oat_db_c_sen.handle}>1.7
SET #{clg_sch_act.handle} = 29.4
SET #{htg_sch_act.handle} = 15.6
ELSE
SET #{clg_sch_act.handle} = NULL
SET #{htg_sch_act.handle} = NULL
ENDIF
EMS
optstart_prg.setBody(optstart_prg_body)

# Program Calling Managers
setup_mgr = OpenStudio::Model::EnergyManagementSystemProgramCallingManager.new(air_loop_hvac.model)
setup_mgr.setName("#{loop_name_clean}OptimumStartCallingManager#{i}")
setup_mgr.setCallingPoint('BeginTimestepBeforePredictor')
setup_mgr.addProgram(optstart_prg)
end
avm_os = OpenStudio::Model::AvailabilityManagerOptimumStart.new(air_loop_hvac.model)
avm_os.setName("#{air_loop_hvac.name.get} Optimum Start Availability Manager")
avm_os.setControlAlgorithm('AdaptiveTemperatureGradient')
# these are defaults, but set here for visibility
avm_os.setInitialTemperatureGradientduringCooling(2)
avm_os.setInitialTemperatureGradientduringHeating(2)
avm_os.setNumberofPreviousDays(3)
# add availability manager
air_loop_hvac.addAvailabilityManager(avm_os)

OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.AirLoopHVAC', "For #{air_loop_hvac.name}: Optimum start control enabled.")

Expand Down