Metrics Reference

Every metric below is sourced from a real snmpwalk against the actual device (HP R/T3000 HV INTL UPS, part number J2R04A, "G4", Eaton-manufactured, HP UPS Network Module AF465A, firmware 1.13.001, UPS microcontroller firmware 01.02.0004), cross-checked against two independent MIB trees where possible. Nothing here is guessed. Where a value could not be verified against the real device, it is not implemented (see "Deliberately excluded" at the end).

Why two MIB trees

This UPS answers on both:

  • Standard UPS-MIB (RFC 1628), OID root 1.3.6.1.2.1.33
  • HP/Compaq CPQPOWER-MIB (proprietary, vendor-recommended), OID root 1.3.6.1.4.1.232.165

CPQPOWER-MIB is used as the primary source — it has HP's own richer data model (Advanced Battery Management state, outlet segment control, real device identity/MAC, self-test control, true Watts). Standard UPS-MIB supplements it for exactly three things CPQPOWER-MIB cannot provide or provides with less precision:

  1. upsAlarmsPresent — CPQPOWER-MIB has no alarm-count OID at all.
  2. upsSecondsOnBattery — CPQPOWER-MIB only reports remaining runtime, never elapsed time already spent on battery.
  3. Output apparent power (VA) and 0.1A-resolution current — CPQPOWER-MIB's own current/apparent-power fields on this unit are whole-number resolution only; standard UPS-MIB gives one more decimal digit, and its VA value paired with CPQPOWER's real-Watts value lets the dashboard show power factor without fabricating anything.

Verification method

Both MIB trees were walked live against the device (10.50.20.3, SNMPv3, user readuser, authNoPriv, MD5). Cross-checks that confirmed the OID map and scaling:

  • Nameplate rating fields (upsConfigOutputVA=3000, upsConfigOutputPower=2700, upsConfigOutputVoltage=230, upsConfigOutputFreq=500→50.0Hz) match the device's own published spec sheet exactly, in both MIB trees independently.
  • upsIdentOemCode = 12 (0x0C), matching the CPQPOWER-MIB's own documented statement that "this should be 0x0c for HP."
  • Input/output voltage (235V) and line-quality counter (Counter32: 5) are identical between the two trees.
  • Battery voltage: standard UPS-MIB reports 770 at 0.1V resolution = 77.0V; CPQPOWER-MIB reports 77 unscaled = 77V. Identical value, confirming CPQPOWER's battery voltage OID is whole-volt resolution (not 0.1V as might be assumed by analogy with other fields) and that 77V is plausible for the reported 6x 12V VRLA series-string battery configuration.
  • Low/high voltage transfer points (160V/294V) match exactly between upsConfigLowVoltageTransferPoint/HighVoltageTransferPoint (standard MIB) and upsConfigLowOutputVoltageLimit/HighOutputVoltageLimit (CPQPOWER-MIB).
  • The device's own real-time clock (CPQPOWER upsConfigDateAndTime) read back the correct current date at walk time, confirming the OID's identity.
  • upsTopoUnitNumber = 0, matching the MIB's documented meaning "standalone units use a value of 0."

Field reference

Measurement: snmp_ups_status (polled every 10s)

Field OID Source MIB Raw type / scaling Meaning
output_source_code 1.3.6.1.4.1.232.165.3.4.5.0 CPQPOWER upsOutputSource INTEGER, no scaling Operating mode enum (see below)
load_percent 1.3.6.1.4.1.232.165.3.4.1.0 CPQPOWER upsOutputLoad INTEGER percent, no scaling Output load, % of rated capacity (2700W)
battery_charge_percent 1.3.6.1.4.1.232.165.3.2.4.0 CPQPOWER upsBatCapacity INTEGER percent, no scaling Battery state of charge
battery_abm_status_code 1.3.6.1.4.1.232.165.3.2.5.0 CPQPOWER upsBatteryAbmStatus INTEGER, no scaling ABM charge-cycle state enum (see below)
battery_runtime_seconds 1.3.6.1.4.1.232.165.3.2.1.0 CPQPOWER upsBatTimeRemaining INTEGER seconds, no scaling Estimated runtime remaining at present load
battery_voltage_volts 1.3.6.1.2.1.33.1.2.5.0 Standard upsBatteryVoltage INTEGER, 0.1V DC (conversion = "float(1)") Battery string voltage
battery_current_amps 1.3.6.1.2.1.33.1.2.6.0 Standard upsBatteryCurrent INTEGER, 0.1A DC (conversion = "float(1)") Positive = discharging, negative = recharging
alarms_present 1.3.6.1.2.1.33.1.6.1.0 Standard upsAlarmsPresent Gauge32, no scaling Count of currently active device alarms
seconds_on_battery 1.3.6.1.2.1.33.1.2.2.0 Standard upsSecondsOnBattery INTEGER seconds, no scaling Elapsed time since the current on-battery event began (0 = on mains)

output_source_code enum (CPQPOWER upsOutputSource / NUT's cpqpower_pwr_info): 1=other, 2=off/none, 3=normal (online, on mains), 4=bypass, 5=battery, 6=booster (online, boosting a sagging input), 7=reducer (online, trimming a high input), 8=parallelCapacity, 9=parallelRedundant, 10=highEfficiencyMode.

battery_abm_status_code enum (CPQPOWER upsBatteryAbmStatus): 1=charging, 2=discharging, 3=floating (topping off to float voltage), 4=resting (fully charged, idle), 5=unknown.

Measurement: snmp_ups_electrical (polled every 20s)

Field OID Source MIB Raw type / scaling Meaning
input_voltage_volts 1.3.6.1.4.1.232.165.3.3.4.1.2.1 CPQPOWER upsInputVoltage (table, phase 1) INTEGER RMS volts, no scaling Mains input voltage
input_current_amps 1.3.6.1.2.1.33.1.3.3.1.4.1 Standard upsInputCurrent (table, line 1) INTEGER, 0.1A (conversion = "float(1)") Mains input current - see "Known open issue" below
input_realpower_watts 1.3.6.1.4.1.232.165.3.3.4.1.4.1 CPQPOWER upsInputWatts (table, phase 1) INTEGER Watts, no scaling Mains real input power - see "Known open issue" below
input_frequency_hz 1.3.6.1.4.1.232.165.3.3.1.0 CPQPOWER upsInputFrequency INTEGER, 0.1Hz (conversion = "float(1)") Mains input frequency
input_source_code 1.3.6.1.4.1.232.165.3.3.5.0 CPQPOWER upsInputSource INTEGER, no scaling Present input source enum (see below)
output_voltage_volts 1.3.6.1.4.1.232.165.3.4.4.1.2.1 CPQPOWER upsOutputVoltage (table, phase 1) INTEGER RMS volts, no scaling Output voltage
output_current_amps 1.3.6.1.2.1.33.1.4.4.1.3.1 Standard upsOutputCurrent (table, line 1) INTEGER, 0.1A (conversion = "float(1)") Output current
output_frequency_hz 1.3.6.1.4.1.232.165.3.4.2.0 CPQPOWER upsOutputFrequency INTEGER, 0.1Hz (conversion = "float(1)") Output frequency
output_realpower_watts 1.3.6.1.4.1.232.165.3.4.4.1.4.1 CPQPOWER upsOutputWatts (table, phase 1) INTEGER Watts, no scaling Output power

input_source_code enum (CPQPOWER upsInputSource): 1=other, 2=none, 3=primaryUtility, 4=bypassFeed, 5=secondaryUtility, 6=generator, 7=flywheel, 8=fuelcell.

This UPS is single-phase (upsInputNumPhases/upsOutputNumPhases = 1 in both MIB trees), so every table OID above is read directly at table index 1 rather than walked as a multi-row table.

Real vs. apparent power (removed after live verification): the design originally pulled output_realpower_watts (Watts, CPQPOWER) alongside output_apparentpower_va (VA, standard UPS-MIB upsOutputPower) on the theory that their ratio would give a real power-factor reading, since a single first-pass snmpwalk of each tree showed different values (216W vs 297W). That comparison was wrong - the two walks were separate, non-atomic commands, and load had simply drifted between them. A live, paired snmpget against both OIDs simultaneously (run several times, at different loads: 270/270, 243/243 x4, 216/216) showed they are always identical. This device's firmware does not actually differentiate real from apparent power - both OIDs source the same internal register. output_apparentpower_va was removed from telegraf.conf and the dashboard as redundant; keeping it would have implied a power-factor insight the hardware doesn't actually provide. This is exactly the kind of thing Phase 5 (live validation) exists to catch - a plausible-looking single-sample cross-check turned out to be an artifact of measurement timing, not a real property of the device.

Measurement: snmp_ups_outlet (polled every 30s, tagged by index = outlet segment 1 or 2)

Field OID (column) Source MIB Raw type / scaling Meaning
status_code 1.3.6.1.4.1.232.165.3.10.2.1.2 CPQPOWER upsRecepStatus INTEGER, no scaling Segment power state enum (see below)
off_delay_seconds 1.3.6.1.4.1.232.165.3.10.2.1.3 CPQPOWER upsRecepOffDelaySecs INTEGER seconds, -1=no shutdown pending Countdown to a commanded shutdown of this segment
on_delay_seconds 1.3.6.1.4.1.232.165.3.10.2.1.4 CPQPOWER upsRecepOnDelaySecs INTEGER seconds, -1=no startup pending Countdown to a commanded startup of this segment
auto_off_delay_seconds 1.3.6.1.4.1.232.165.3.10.2.1.5 CPQPOWER upsRecepAutoOffDelay INTEGER seconds, -1=never Configured delay before this segment auto-sheds after going on battery (load-shedding priority)
auto_on_delay_seconds 1.3.6.1.4.1.232.165.3.10.2.1.6 CPQPOWER upsRecepAutoOnDelay INTEGER seconds, -1=never Configured delay before this segment auto-restores after mains returns

This UPS has exactly 2 independently controllable outlet segments (upsNumReceptacles = 2, matching the device's published "2 independent load segments" spec), each hardcoded as its own dashboard panel rather than a repeated/templated panel, since the count is fixed hardware.

status_code enum (CPQPOWER upsRecepStatus): 1=on, 2=off, 3=pendingOff, 4=pendingOn, 5=unknown.

Measurement: snmp_ups_identity (polled every 300s — static/rarely-changing data)

Field OID Source MIB Meaning
manufacturer 1.3.6.1.4.1.232.165.3.1.1.0 CPQPOWER upsIdentManufacturer Real UPS manufacturer ("EATON" — HP/HPE rebadges Eaton-built hardware for this model)
model 1.3.6.1.4.1.232.165.3.1.2.0 CPQPOWER upsIdentModel Model string
ups_firmware_version 1.3.6.1.4.1.232.165.3.1.3.0 CPQPOWER upsIdentSoftwareVersions UPS microcontroller firmware
oem_code 1.3.6.1.4.1.232.165.3.1.4.0 CPQPOWER upsIdentOemCode Vendor code (12/0x0C = HP, per MIB documentation)
serial_number 1.3.6.1.4.1.232.165.1.2.7.0 CPQPOWER deviceSerialNumber UPS serial number
nmc_manufacturer 1.3.6.1.4.1.232.165.1.2.1.0 CPQPOWER deviceManufacturer Network management card manufacturer
nmc_model 1.3.6.1.4.1.232.165.1.2.2.0 CPQPOWER deviceModel Network management card model name
nmc_firmware_version 1.3.6.1.4.1.232.165.1.2.3.0 CPQPOWER deviceFirmwareVersion Network management card firmware
nmc_hardware_version 1.3.6.1.4.1.232.165.1.2.4.0 CPQPOWER deviceHardwareVersion Network management card hardware revision
device_ident_name 1.3.6.1.4.1.232.165.1.2.5.0 CPQPOWER deviceIdentName Internal product identifier (e.g. USVHPRT3000G4)
nmc_part_number 1.3.6.1.4.1.232.165.1.2.6.0 CPQPOWER devicePartNumber Network management card part number (AF465A)
nmc_mac_address 1.3.6.1.4.1.232.165.1.2.8.0 CPQPOWER deviceMACAddress Network management card MAC address
test_result_code 1.3.6.1.4.1.232.165.3.7.2.0 CPQPOWER upsTestBatteryStatus Last self-test result enum (see below)
nominal_output_voltage_volts 1.3.6.1.4.1.232.165.3.9.1.0 CPQPOWER upsConfigOutputVoltage Nameplate output voltage
nominal_input_voltage_volts 1.3.6.1.4.1.232.165.3.9.2.0 CPQPOWER upsConfigInputVoltage Nameplate input voltage
nominal_output_power_watts 1.3.6.1.4.1.232.165.3.9.3.0 CPQPOWER upsConfigOutputWatts Nameplate real power rating (2700W)
nominal_output_frequency_hz 1.3.6.1.4.1.232.165.3.9.4.0 CPQPOWER upsConfigOutputFreq Nameplate frequency, 0.1Hz (conversion = "float(1)")
low_voltage_transfer_volts 1.3.6.1.4.1.232.165.3.9.6.0 CPQPOWER upsConfigLowOutputVoltageLimit Input voltage below which the UPS transfers to battery
high_voltage_transfer_volts 1.3.6.1.4.1.232.165.3.9.7.0 CPQPOWER upsConfigHighOutputVoltageLimit Input voltage above which the UPS transfers to battery
low_battery_runtime_minutes 1.3.6.1.2.1.33.1.9.7.0 Standard upsConfigLowBattTime Device's own "low battery" runtime warning threshold (minutes) — drives the Runtime Remaining gauge's red threshold
outlet_count 1.3.6.1.4.1.232.165.3.10.1.0 CPQPOWER upsNumReceptacles Number of independently controllable outlet segments

test_result_code enum (CPQPOWER upsTestBatteryStatus): 1=unknown, 2=passed, 3=failed, 4=inProgress, 5=notSupported, 6=inhibited, 7=scheduled.

Known open issue: input current/power reads 0 on this specific unit

input_current_amps and input_realpower_watts have so far always read 0 on this device, across every check performed: the original snmpwalk, hours of dashboard history, and several live triple-snmpget runs at different loads, including moments where output power was simultaneously confirmed non-zero (~250W) - which rules out these OIDs simply being wrong or the field being zero because nothing is drawing power.

This was initially written up as a hardware limitation ("this line-interactive UPS has no input-side current sensor"), but that conclusion doesn't hold up under research:

  • A different real HP R/T3000 G2 unit, on the identical CPQPOWER-MIB tree, is documented (networkupstools.org) reporting input.current: 0.40 - a working, non-zero value.
  • Other AF465A-carded HP UPS units (per a NUT mailing-list thread) report non-zero per-phase input current.
  • An HPE community thread has another R/T3000 owner reporting non-zero (even higher-than-output) input current.

So input current metering is clearly supported by this MIB/hardware family in general - it is very likely something specific to this unit (it was purchased used, with a known pre-existing battery defect, so a faulty or disconnected input CT wouldn't be a stretch) or a bug specific to this G4 firmware build, rather than a documented limitation of the model line. No firmware changelog, HPE/Eaton documentation, or AF465A metering config toggle addressing this was found either way.

The fields are kept in telegraf.conf and the dashboard rather than removed, since polling them costs nothing and the graphs will simply start working with no config changes if this ever gets resolved (firmware update, hardware repair, or an HPE/Eaton support case). Each panel/field is annotated with this caveat rather than presented as a confirmed working measurement.

Deliberately excluded

  • Ambient/environmental temperature and humidity (upsEnvAmbientTemp and related OIDs under CPQPOWER 1.3.6.1.4.1.232.165.3.6). The device answers these OIDs, but the temperature reading and its configured lower limit both read back a flat 0, while the upper limit reads a plausible default (40) — the classic signature of an optional temperature/humidity probe accessory that is not physically connected to the network management card. Rather than build a panel around a phantom 0°C reading, these were left out. If a probe is later connected, the OIDs are already known (see the CPQPOWER-MIB upsEnvironment group) and can be added.
  • upsBatteryTemperature (standard UPS-MIB, 1.3.6.1.2.1.33.1.2.7.0) — also reads a flat 0, same reasoning.
  • UPS topology group (upsTopologyType, upsTopoMachineCode, upsTopoUnitNumber, upsTopoPowerStrategy) — exists and was read (upsTopoUnitNumber = 0, correctly indicating a standalone, non-parallel unit), but has no practical monitoring value for a single standalone UPS; it only matters for parallel/modular UPS installations.
  • Bypass voltage/frequency table (upsBypassFrequency/upsBypassNumPhases, both read as 0) — this line-interactive unit has no separately-metered bypass line, so there is nothing to graph.
  • Control-group delay OIDs at the system level (upsControlOutputOffDelay etc.) and the battery/trap self-test command OIDs (upsTestBattery, upsTestTrap) — these are write-only command triggers, not metrics; polling them just reads back whatever was last set (usually 0/disabled) and provides no monitoring value. The equivalent per-outlet delay values are polled instead, since those are genuinely informative.

Thresholds: device-reported vs. engineering defaults

Threshold Value Source
Voltage transfer limits (input/output gauges) 160V / 294V Device-reported — upsConfigLowOutputVoltageLimit/HighOutputVoltageLimit, confirmed identical in both MIB trees
Runtime "critical" threshold 180s (3 min) Device-reported — standard UPS-MIB upsConfigLowBattTime = 3 minutes
Load "warning"/"critical" 80% / 100% Engineering default — 100% = nameplate-rated capacity (2700W), a standard UPS monitoring convention
Battery charge "warning"/"critical" 50% / 20% Engineering default — the device does not expose a percent-based low-battery threshold (only the time-based one above)
Frequency acceptable band 50Hz ± 3% (48.5–51.5Hz "green", 47–53Hz "yellow") Engineering default — neither MIB tree exposes a frequency transfer-limit OID for this model
Voltage nominal band 230V ± 10% (207–253V "green") Engineering default overlay inside the device-reported transfer limits

Polling intervals

Block Interval Rationale
snmp_ups_status 10s Everything needed to reconstruct a power event minute-by-minute: operating mode, battery state/voltage/current/charge/runtime, alarms, elapsed time on battery
snmp_ups_electrical 20s Input/output voltage, current, frequency, power — changes more gradually than battery state under normal conditions
snmp_ups_outlet 30s Outlet segment status changes only during a shutdown/restart sequence
snmp_ups_identity 300s Static nameplate/identity data that only changes on a firmware or hardware change